ViroSafe 2500/F1000

Mobile air purification for clean areas

The ViroSafe 2500 filters dust and airborne particles from room air. It is suitable for production areas where low-particle air is required, for example in assembly or packaging.

  • Up to 2,500 m³ of filtered air per hour
  • Class H14 HEPA filter
  • Recirculation mode, optionally positive or negative pressure via an air duct connection

€3,498.00 plus VAT

€4,162.62 incl. VAT

ViroSafe 2500/F1000 mobile air purifier with HEPA H14 filter by Viromed

When is a clean area sufficient for production?

If dust is a problem during assembly or packaging, it may be sufficient to reduce the particle load in an existing production area. What matters is which air cleanliness requirements apply to your process. If a specific cleanroom class is mandatory, it must be verified for the room.

The ViroSafe 2500 can be set up in the existing room. In recirculation mode, it draws in room air, filters dust and airborne particles through a HEPA H14 filter and releases the cleaned air back into the room. No air duct connection is required for this mode.

Clean area and cleanroom compared

Feature

Classified cleanroom

Clean area with ViroSafe 2500

Requirement

The process requires a defined and verified ISO cleanliness class.

Dust and airborne particles in the production air are to be reduced.

Installation

The room and ventilation system are designed for the required cleanliness.

Mobile filter unit on casters. In recirculation mode, a power connection is all that is needed.

Pressure control

Pressure cascades depend on the room concept.

Positive or negative pressure is optionally possible via an air duct connection.

Operation

Compliance with the required cleanliness class is verified by measurements.

Filters and UV lamp are replaced according to the maintenance indicator. The air cleanliness achieved can be measured on site.

What air cleanliness does my production area achieve?

The ISO specification in the data sheet refers to the filtered supply air of the ViroSafe 2500. How many particles remain in the work area depends, among other things, on the room volume and on how much dust is generated during production. This can be checked with an on-site particle measurement.

How the ViroSafe 2500 filters room air

ViroSafe 2500 opened: pre-filter, compact filter, fan and UV lamps

Opened ViroSafe 2500 with pre-filter, compact filter and fan. UV lamps irradiate the pre-filters.

  1. 1

    Drawing in room air and capturing coarse dust

    The unit draws in room air at the bottom. A replaceable F5 pre-filter captures coarser dust particles.

  2. 2

    Separating finer particles

    An F7 compact filter retains finer particles, relieving the downstream HEPA filter.

  3. 3

    Retaining airborne particles in the HEPA filter

    The air flows through the H14 main filter. For this filter, the manufacturer specifies a separation efficiency of 99.995% at a particle size of 0.3 µm.

  4. 4

    Returning filtered air to the room

    The cleaned air exits through the air diffuser at the top. During operation, the unit continuously draws in more room air at the bottom.

Recirculation, positive pressure or negative pressure

Diagram of recirculation mode: ViroSafe 2500 draws in room air at the bottom and releases HEPA-filtered air at the top

Standard

Recirculation mode

The ViroSafe 2500 filters the existing room air and returns it, cleaned, to the same room. This is suitable for production areas where less dust and fewer airborne particles are desired.

Diagram of positive pressure mode: filtered fresh air creates positive pressure, air flows out into the corridor

Optional

Positive pressure mode

Via an air duct, the unit additionally supplies filtered outdoor air. With positive pressure, air flows from the clean area into adjacent areas. This reduces the ingress of dust, for example from a neighboring production area.

Diagram of negative pressure mode: filtered exhaust air is discharged outside, air flows in from the corridor

Optional

Negative pressure mode

The unit discharges part of the room air to the outside through an H13 filter. With negative pressure, air flows into the room from adjacent areas. This limits the spread of airborne particles into neighboring areas.

Measurements by the Bundeswehr University Munich

How quickly does the particle concentration in the room decrease?

The Bundeswehr University Munich examined the predecessor model ViroSafe 2000/F800 in an 80 m² test room with a room volume of 200 m³. The research team introduced aerosol particles into the room air and measured how quickly their concentration decreased.

Operating mode

Time until the particle concentration is halved

Recirculation at the highest setting

5.4 minutes

With outdoor air supply and additional fan

4.2 minutes

The values apply to the test room. How high the particle concentration remains during ongoing production depends, among other things, on how much new dust enters the air during production.

Viromed provided the unit for the measurement in the 80 m² room and financially supported the study.

ViroSafe 2500/F1000 technical data

Product brochure with technical data (PDF)

Feature

Value

Recircu­lation capacity

Up to 2,500 m³/h

Outdoor air supply (optional)

Up to 1,000 m³/h via air duct connection

Main filter

HEPA H14 according to EN 1822, 30 m² filter area

Main filter separation efficiency

99.995% at 0.3 µm according to the manufacturer

Pre-filter

Disposable F5 pre-filter and F7 compact filter with 8.5 m² filter area

Airflow

Turbulent flow at 0.3–1.5 m/s at the air outlet

Sound level at 1 m distance

Below 50 dB(A) in normal mode, below 42 dB(A) in economy mode

Power supply

230 V, 50 Hz

Power con­sumption

200 W for the filter fan unit, 30 W for the UV lamp

Dimensions (W × D × H)

717 × 513 × 2.000 mm

Weight

90 kg

Housing

Steel, internal structure made of aluminum, each with an antibacterial epoxy powder coating

Controlling air output and monitoring filters

  • Schedule operating times. Daily and weekly on and off times can be set via the touch control panel.
  • Set the airflow rate. The desired air output can be selected on the unit or by remote control. The control system automatically adjusts the airflow rate.
  • Check the filter status. The display shows the remaining service life of the HEPA filter as a percentage, as well as the operating hours of the fan and UV lamp.
  • Recognize maintenance needs. The unit monitors the airflow rate and gives visual and acoustic warnings in the event of deviations. It also indicates when a filter change, lamp change or maintenance is due.

Where the ViroSafe 2500 is used

Production

For assembly, filling and packaging, when dust in the room air can contaminate components or open products.

Laboratories

Cell culture and molecular biology laboratories as well as work areas where particles interfere with samples or measurements.

Medicine and care

Infection control areas, isolation of immunocompromised or infectious patients, treatment and procedure rooms, dentistry, intensive care and neonatal units.

Frequently asked questions about clean areas and the ViroSafe 2500

What is a clean area and how does it differ from a cleanroom?

In a clean area, a company limits the ingress of dust and other particles, for example to protect sensitive components during assembly. How clean the area needs to be depends on the production process. In a classified cleanroom, measurements verify that the particle concentration in the air complies with the limits of the required ISO class.

Can the ViroSafe 2500 replace a cleanroom?

If your process requires low-particle air, the ViroSafe 2500 can reduce the particle load through HEPA filtration. If a specific cleanroom class is mandatory, verification must be provided for the room itself. The unit’s filter class alone is not sufficient for this.

How many units do I need for my production room?

The key factors for sizing are room volume, the desired air change rate and dust ingress during ongoing operation. When you send your inquiry, tell us the floor area, the room height and the work step in which dust is a problem. This allows us to estimate the right number of units for your room.

How much does the ViroSafe 2500 cost?

The ViroSafe 2500 costs €3,498.00 plus VAT (€4,162.62 incl. VAT). For a configuration with a positive or negative pressure module or for multiple units, we will prepare an individual quote for you.

Inquire about the ViroSafe 2500

We advise you on room size, air change rate, operating mode and number of units and prepare a quote for you.