Production
For assembly, filling and packaging, when dust in the room air can contaminate components or open products.
ViroSafe 2500/F1000
The ViroSafe 2500 filters dust and airborne particles from room air. It is suitable for production areas where low-particle air is required, for example in assembly or packaging.
€3,498.00 plus VAT
€4,162.62 incl. VAT

If dust is a problem during assembly or packaging, it may be sufficient to reduce the particle load in an existing production area. What matters is which air cleanliness requirements apply to your process. If a specific cleanroom class is mandatory, it must be verified for the room.
The ViroSafe 2500 can be set up in the existing room. In recirculation mode, it draws in room air, filters dust and airborne particles through a HEPA H14 filter and releases the cleaned air back into the room. No air duct connection is required for this mode.
Feature
Classified cleanroom
Clean area with ViroSafe 2500
Requirement
The process requires a defined and verified ISO cleanliness class.
Dust and airborne particles in the production air are to be reduced.
Installation
The room and ventilation system are designed for the required cleanliness.
Mobile filter unit on casters. In recirculation mode, a power connection is all that is needed.
Pressure control
Pressure cascades depend on the room concept.
Positive or negative pressure is optionally possible via an air duct connection.
Operation
Compliance with the required cleanliness class is verified by measurements.
Filters and UV lamp are replaced according to the maintenance indicator. The air cleanliness achieved can be measured on site.
What air cleanliness does my production area achieve?
The ISO specification in the data sheet refers to the filtered supply air of the ViroSafe 2500. How many particles remain in the work area depends, among other things, on the room volume and on how much dust is generated during production. This can be checked with an on-site particle measurement.

Opened ViroSafe 2500 with pre-filter, compact filter and fan. UV lamps irradiate the pre-filters.
The unit draws in room air at the bottom. A replaceable F5 pre-filter captures coarser dust particles.
An F7 compact filter retains finer particles, relieving the downstream HEPA filter.
The air flows through the H14 main filter. For this filter, the manufacturer specifies a separation efficiency of 99.995% at a particle size of 0.3 µm.
The cleaned air exits through the air diffuser at the top. During operation, the unit continuously draws in more room air at the bottom.

Standard
The ViroSafe 2500 filters the existing room air and returns it, cleaned, to the same room. This is suitable for production areas where less dust and fewer airborne particles are desired.

Optional
Via an air duct, the unit additionally supplies filtered outdoor air. With positive pressure, air flows from the clean area into adjacent areas. This reduces the ingress of dust, for example from a neighboring production area.

Optional
The unit discharges part of the room air to the outside through an H13 filter. With negative pressure, air flows into the room from adjacent areas. This limits the spread of airborne particles into neighboring areas.
Measurements by the Bundeswehr University Munich
The Bundeswehr University Munich examined the predecessor model ViroSafe 2000/F800 in an 80 m² test room with a room volume of 200 m³. The research team introduced aerosol particles into the room air and measured how quickly their concentration decreased.
Operating mode
Time until the particle concentration is halved
Recirculation at the highest setting
5.4 minutes
With outdoor air supply and additional fan
4.2 minutes
The values apply to the test room. How high the particle concentration remains during ongoing production depends, among other things, on how much new dust enters the air during production.
Viromed provided the unit for the measurement in the 80 m² room and financially supported the study.
Feature
Value
Recirculation capacity
Up to 2,500 m³/h
Outdoor air supply (optional)
Up to 1,000 m³/h via air duct connection
Main filter
HEPA H14 according to EN 1822, 30 m² filter area
Main filter separation efficiency
99.995% at 0.3 µm according to the manufacturer
Pre-filter
Disposable F5 pre-filter and F7 compact filter with 8.5 m² filter area
Airflow
Turbulent flow at 0.3–1.5 m/s at the air outlet
Sound level at 1 m distance
Below 50 dB(A) in normal mode, below 42 dB(A) in economy mode
Power supply
230 V, 50 Hz
Power consumption
200 W for the filter fan unit, 30 W for the UV lamp
Dimensions (W × D × H)
717 × 513 × 2.000 mm
Weight
90 kg
Housing
Steel, internal structure made of aluminum, each with an antibacterial epoxy powder coating
For assembly, filling and packaging, when dust in the room air can contaminate components or open products.
Cell culture and molecular biology laboratories as well as work areas where particles interfere with samples or measurements.
Infection control areas, isolation of immunocompromised or infectious patients, treatment and procedure rooms, dentistry, intensive care and neonatal units.
In a clean area, a company limits the ingress of dust and other particles, for example to protect sensitive components during assembly. How clean the area needs to be depends on the production process. In a classified cleanroom, measurements verify that the particle concentration in the air complies with the limits of the required ISO class.
If your process requires low-particle air, the ViroSafe 2500 can reduce the particle load through HEPA filtration. If a specific cleanroom class is mandatory, verification must be provided for the room itself. The unit’s filter class alone is not sufficient for this.
The key factors for sizing are room volume, the desired air change rate and dust ingress during ongoing operation. When you send your inquiry, tell us the floor area, the room height and the work step in which dust is a problem. This allows us to estimate the right number of units for your room.
The ViroSafe 2500 costs €3,498.00 plus VAT (€4,162.62 incl. VAT). For a configuration with a positive or negative pressure module or for multiple units, we will prepare an individual quote for you.
We advise you on room size, air change rate, operating mode and number of units and prepare a quote for you.
Phone
Advice
Orders